Enclosure for Mobile Substation
General Description of the Mobile Substation Enclosure
Cabinet type: Modular frame structure
Material: Galvanized sheet steel with powder coating
Thickness:
-
Base frame and top frame: ≥ 3 mm
-
Cabinet body and roof panels: ≥ 2 mm
Base: 2 U-shaped steel bars, load capacity ≥ 4 tons
Protection rating: IP54
Dimensions (W × H × D): W3500 × H2300 × D2100
- Description
Description
General Description of the Mobile Substation Enclosure
Cabinet type: Modular frame structure
Material: Galvanized sheet steel with powder coating
Thickness:
-
Base frame and top frame: ≥ 3 mm
-
Cabinet body and roof panels: ≥ 2 mm
Base: 2 U-shaped steel bars, load capacity ≥ 4 tons
Protection rating: IP54
Dimensions (W × H × D): W3500 × H2300 × D2100
Substation Enclosure:
-
Made of galvanized sheet steel with powder coating.
-
Manufactured in compliance with IEC60349-1, IEC62271-200, and IEC1330:1995 standards.
-
Designed with IP54 protection (for medium-voltage compartment, low-voltage compartment, and transformer compartment).
-
Equipped with lifting hooks suitable for transportation.
-
Partition walls made of sheet steel with a minimum thickness of 1.5 mm. There are two partitions: one between the medium-voltage and transformer compartments, and one between the transformer and low-voltage compartments. Partitions include supports for MV and LV cables.
-
Doors for the MV compartment, transformer compartment, and LV compartment are double-leaf (02 doors), with strong fire-resistant steel hinges, locks, handles, and safety warning signs. Doors are equipped with stoppers to prevent sudden slamming. Doors are sealed with a lock system and gaskets to prevent water ingress and insect entry.
-
Enclosure is corrosion- and rust-resistant, made from steel with a minimum thickness of 2 mm, powder-coated on both inner and outer surfaces, and sized appropriately for installation of equipment (transformers, etc.) and connections, compliant with international safety standards and continuous operation requirements.
Base frame:
-
The base is a load-bearing frame supporting all substation equipment. Made from 3.5 mm galvanized sheet steel, powder-coated on both sides. Includes two U-shaped steel beams supporting the transformer, all interconnected with welded joints and bolts, hot-dip galvanized, with the outer surface painted black.
Roof:
-
Made of galvanized sheet steel, powder-coated on both inner and outer surfaces for outdoor use.
-
Roof is welded securely to the enclosure.
-
Roof includes four anchor points for lifting operations.
-
Roof has a minimum slope of 2% to ensure no water accumulation.